Before opening the instrument
01Documents
Match the tag to the loop drawing, datasheet, range, alarm or trip setpoints, tolerance, work instruction and hazardous-area dossier.
02Process effects
Identify displays, controllers, permissives, shutdown logic, voting, historian values and final elements affected by the test.
03Test equipment
Check identity, calibration status, range, accuracy, leads, hoses, fittings, batteries and pressure rating.
04As-found condition
Record damage, corrosion, loose entries, blocked paths, diagnostics, configuration and initial indication before adjustment.
Choose the connection before touching the loop
Black lead returns to common.
Red lead for current measurement or output.
Red lead for voltage, resistance or sensor simulation.
Parallel for voltage and HART.
Critical: Never place a meter in current mode directly across a powered source. Confirm lead sockets, selected function, loop voltage, approved test point and hazardous-area suitability before connection.
mAMeasure a live 4–20 mA loop
Connection: meter in series at an approved break or test point.
- Confirm the loop can be opened and identify the effect on indication, control and trips.
- Black lead to COM; red lead to the fused mA input; select DC mA.
- Open the approved point and bridge the gap through the meter so all loop current passes through it.
- Verify polarity, read the value, then remove the meter and fully restore the original conductor path.
- Confirm the loop indication and affected logic return to normal.
Do not: connect across positive and negative like a voltmeter. That can short the loop or rupture the meter fuse.
VMeasure DC loop voltage
Connection: meter in parallel across two defined points while the loop remains intact.
- Black lead to COM; red lead to V/Ω; select DC volts.
- Confirm the expected voltage and meter rating.
- Place the leads across the supply, transmitter terminals, resistor or input points identified by the loop drawing.
- Compare measured polarity and voltage with the expected loop-power distribution.
- Remove probes without disturbing conductors and confirm covers or test points are restored.
Use for: checking supply presence, voltage drop and whether enough voltage remains for the transmitter and barriers.
SRCSource 4–20 mA into an input
Connection: calibrator becomes the current source for an isolated receiving circuit.
- Obtain approval for simulation and identify every display, alarm, trip, permissive or control action affected.
- Isolate the field transmitter at the authorised boundary.
- Connect source positive and negative to the receiving circuit with the documented polarity.
- Select source mA and apply approved points such as 4, 8, 12, 16 and 20 mA.
- Verify indication and logic at each point, return to a safe value, disconnect and restore field wiring.
Do not: source into a circuit that is still being actively driven by another source.
SIMSimulate a two-wire transmitter
Connection: calibrator controls current but uses the loop’s existing external power.
- Confirm the loop power remains available and the transmitter can be removed from the circuit.
- Connect the calibrator at the authorised transmitter boundary with correct polarity.
- Select mA simulate—not source or measure.
- Apply the required current points and verify the complete receiving path.
- Return to a safe value, disconnect, restore the transmitter and confirm live operation.
Difference: simulate needs external loop power; source mode supplies the current itself.
PWRPower and measure a two-wire transmitter
Connection: calibrator supplies loop power and measures current in the same isolated circuit.
- Isolate the transmitter from site loop power and verify the approved bench or field-test boundary.
- Connect loop-power positive to transmitter positive and the return path to the calibrator negative input as shown by the manufacturer.
- Select loop-power/mA mode and confirm the configured supply voltage.
- Apply the process input and compare transmitter current with the expected output.
- Remove loop power before disconnecting, then restore original wiring and site power.
Do not: apply calibrator loop power on top of an energised site supply.
HARTConnect a HART communicator
Connection: communicator in parallel across an approved loop point; analogue current remains complete.
- Confirm the device is HART-capable and communication is permitted.
- Connect communicator leads across the transmitter or approved resistor/test points.
- Verify the loop has the required resistance and stable power for communication.
- Read identity, range, units, damping and diagnostics before changing anything.
- Make only authorised configuration changes, save evidence and verify the analogue output afterward.
Remember: successful digital communication does not prove the process sensor or 4–20 mA path is accurate.
PTPressure transmitter complete setup
Connection: rated pressure source and reference on the process side; suitable mA measurement or loop-power mode on the electrical side.
- Prove process isolation, depressurisation and the safe vent path.
- Fit rated hoses and adapters without loading the transmitter body or manifold.
- Leak-check the pressure setup before applying test points.
- Apply pressure upscale and downscale while recording input, mA output and control-system indication.
- Vent safely, remove pressure, restore valves and fittings, leak-check and confirm live indication.
DP units: follow the approved manifold sequence and protect the low-pressure side from overpressure.
TTRTD or thermocouple simulation
Connection: calibrator at the authorised sensor terminal boundary using the configured sensor type and wire arrangement.
- Confirm RTD type and 2/3/4-wire arrangement, or thermocouple type and cold-junction method.
- Disconnect the field sensor only after recording the as-found condition.
- Black and red leads use the V/Ω or dedicated temperature terminals required by the calibrator.
- Select the exact sensor type and apply approved temperature points across the range.
- Restore polarity and lead arrangement, tighten correctly, close the enclosure and verify ambient process indication.
Do not: mix thermocouple extension materials, ignore cold-junction compensation or short out RTD lead compensation.
Connection boundary: These sequences are conceptual. Terminal numbers, barriers, fusing, grounding, intrinsic-safety limits and isolation details come only from the current loop drawing, device manual and approved site method.
Work instruction rehearsals
Select a task and follow the sequence. Site-specific isolation and reinstatement steps always take precedence.
PTPressure transmitter
- Confirm the process isolation and safe depressurisation route with operations.
- Record the as-found process value, output signal and physical condition.
- Connect the pressure standard using rated fittings and the approved leak-free test point.
- Apply 0, 25, 50, 75 and 100% inputs, then repeat downscale without overshoot.
- Adjust only when authorised and justified by the complete as-found data set.
- Restore the process connection, leak-check, remove overrides and confirm the live indication.
FTDP flow transmitter
- Confirm whether square-root extraction is in the transmitter or control system.
- Use the approved manifold sequence; do not improvise equalisation under differential pressure.
- Apply differential-pressure inputs that correspond to the required flow test points.
- Compare the raw DP, transmitter output and displayed flow at each point.
- Check zero only under a proven equalised condition, not merely because the display looks low.
- Return the manifold to service position and verify the process response with operations.
TTTemperature transmitter
- Identify the sensor type, range, wiring arrangement and configured cold-junction compensation.
- Inspect terminal condition and record sensor or loop resistance before disturbing wiring.
- Simulate the approved RTD resistance or thermocouple millivolt input with correct lead configuration.
- Check the transmitter output and control-system value across the range.
- Reconnect with correct polarity and terminal torque, then confirm ambient compensation assumptions.
- Close the enclosure correctly and preserve the certified hazardous-area installation.
LTDP level transmitter
- Establish whether the installation uses an open tank, dry leg, wet leg, capillaries or remote seals.
- Confirm the calculated zero elevation or suppression before applying any adjustment.
- Protect filled capillaries from sharp bends, unequal heating and mechanical strain.
- Simulate the approved differential-pressure points and compare against expected level.
- Check for plugged legs, vapour pockets, lost wet-leg fill or unequal impulse-line temperature.
- Restore all valves to documented service position and verify against an independent level indication.
Linear 4–20 mA record
| Point | Applied input | Ideal output | As found | Error | Result |
|---|---|---|---|---|---|
| 0% | 4.000 mA | — | Not entered | ||
| 25% | 8.000 mA | — | Not entered | ||
| 50% | 12.000 mA | — | Not entered | ||
| 75% | 16.000 mA | — | Not entered | ||
| 100% | 20.000 mA | — | Not entered |