Impulse lines
Carry process pressure to pressure, level and DP-flow transmitters.
Every transmitter, analyser and control valve depends on a small-bore line that someone cut, bent and made up by hand. Learn to select the right tube, make up compression fittings correctly, route impulse lines so they read true, and prove the connection is leak-tight.
Tick each lesson as you finish it. Your progress is saved in this browser.
Tubing connects the process to the instrument. If it leaks, blocks, traps gas or liquid, or is mixed with the wrong fitting, the instrument reads wrongly — and the control system acts on a false value. On high-pressure or hazardous service, a failed fitting is also a direct release of energy and fluid.
Carry process pressure to pressure, level and DP-flow transmitters.
Instrument air to positioners, actuators and I/P converters.
Deliver representative process fluid to analysers and sample points.
Wellhead control, chemical injection and hydraulic actuators at high pressure.
Tube is always specified by outside diameter (OD) and wall thickness. The OD must match the fitting exactly; the wall thickness and material set the pressure rating. Take ratings only from the manufacturer's current tables, and apply any temperature derating.
| Material | Typical use | Watch for |
|---|---|---|
| 316 stainless steel | Most process impulse, sample and hydraulic lines | Chloride pitting and crevice corrosion in marine or coastal environments |
| Alloy 625 / 825, super-duplex | Offshore, sour or high-chloride service | Needs matching fitting material and specialised tooling |
| Copper | Low-pressure instrument air in benign areas | Not for hydrocarbon or high-pressure service in most specifications |
| Plastic (nylon, PFA, PE) | Air signal, chemical sample, low pressure | Temperature limits, UV damage, needs tube inserts in some fittings |
Tube must be softer than the fitting. The ferrules have to bite into and swage the tube. Use fully annealed, seamless or welded-and-drawn tube within the maximum hardness recommended by the fitting manufacturer.
Several metric and imperial sizes differ by less than half a millimetre. A 6 mm tube forced into a ¼ in fitting may hold on the bench, then blow out under pressure.
Many manufacturers identify metric nuts and bodies with a stepped shoulder. Never mix metric and imperial components, and never mix components from different manufacturers.
Pipe is sized by a nominal size and a schedule: NPS under the American system, DN in Europe, or NB under the old British system — in Australia you will usually hear "50NB Schedule 40S". Nominal sizes are not the real OD, and the systems differ: size 65 pipe is 73.0 mm OD under the American system but 76.2 mm under the British one.
Tube is sized by its actual OD and wall thickness. Quality depends on OD and ID tolerance, concentricity, hardness, material and wall thickness — every one of them affects whether a compression fitting grips and seals.
Read the roll-stamping: material grade, minimum Mo content, heat number, vendor, OD, wall and seamless or welded. If the marking is incomplete or unreadable, measure OD and wall with callipers, and trace the heat number to the material certificate before using the tube.
Bright annealed (BA) tube looks shiny — but so does polished tube, which may have been work-hardened by polishing past the limit for compression fittings. Welded tube can also look identical to seamless BA tube, yet has a lower maximum allowable working pressure. If you can't verify it from the marking and certificate, don't install it.
| Common name | UNS | ASTM (tube) | Max. hardness (HRB / HV) |
|---|---|---|---|
| 316 / 316L | S31600 / S31603 | A269 / A213 | 90 / 185 |
| 6Mo super-austenitic | S31254 | A269 | 95 / 210 |
| Monel 400 | N04400 | B163 / B165 | 75 / 138 |
| Titanium Grade 2 | R50400 | B338 | 85 / 162 |
| Hastelloy C276 | N10276 | B622 | 100 / 248 |
| Hastelloy B2 | N10665 | B622 | 98 / 241 |
| Inconel 625 | N06625 | B167 / B444 | 95 / 214 |
Hardness limits vary between standards, projects and fitting manufacturers — the purchase specification is often tighter than the ASTM maximum (for example 80 HRB for 316 instrument tube). Always use the tighter figure.
Stainless steel resists corrosion because its chromium (above about 10.5%) reacts with oxygen to form a very thin, invisible chromium-oxide film. Nickel and molybdenum strengthen it. Scratches, dents, weld spatter, grinding swarf and carbon-steel contact all damage that film — and a scratch where the ferrule seats can also stop the fitting sealing.
Working pressures for annealed seamless 316 tube (ASTM A213/A269, max. 80 HRB) at ambient temperature. On gas service, don't select a thin wall that falls in the shaded (gas-excluded) area.
Typical manufacturer chart values in psig. Apply temperature derating, and use your project's tubing data sheet — site values can be lower (see the site example below).
Project specifications set the material and wall for each service. On the example project, 6Mo (UNS S31254, max. 90 HRB) is the offshore standard for general hydrocarbon, hydraulic and instrument-air tubing. Onshore, 6Mo is required where the maximum process temperature is above 50 °C or in near-shore areas (jetty, offsites — BOG compressors, LNG, LPG and condensate storage, tankage flare, drainage and effluent treatment — and the MOF area), and Inconel 625 above 315 °C. Monel 400, Hastelloy C276 or Titanium Grade 2 are used for seawater, cooling and firewater services.
| OD | Wall | MAWP |
|---|---|---|
| ¼ in | 0.049 in | 51 720 kPa (7500 psig) |
| ⅜ in | 0.065 in | 44 820 kPa (6500 psig) |
| ½ in | 0.065 in | 35 170 kPa (5100 psig) |
| ½ in | 0.083 in | 46 200 kPa (6700 psig) |
| ¾ in | 0.049 in | 16 550 kPa (2400 psig) |
| 1 in | 0.065 in | 16 550 kPa (2400 psig) |
| OD | Wall | MAWP |
|---|---|---|
| ⅛ in | 0.035 in | 70 000 kPa |
| ¼ in | 0.049 in | 52 000 kPa |
| ⅜ in | 0.065 in | 45 000 kPa |
| ½ in | 0.083 in | 43 000 kPa |
| ¾ in | 0.083 in | 27 000 kPa |
| 1 in | 0.083 in | 20 000 kPa |
| OD | General (to 1500#) | High pressure (2500#) |
|---|---|---|
| ¼ in | 0.035 in · 19 300 kPa | — |
| ⅜ in | 0.049 in · 18 000 kPa | 0.049 in · 27 000 kPa |
| ½ in | 0.065 in · 17 900 kPa | 0.065 in · 24 000 kPa |
| ¾ in | 0.083 in · 14 000 kPa | 0.083 in · 20 700 kPa |
| 1 in | 0.083 in · 11 000 kPa | — |
| Material | OD × wall | MAWP |
|---|---|---|
| Monel 400 | ¼ × 0.035 · ⅜ × 0.049 · ½ × 0.065 | 33 100 · 30 340 · 30 340 kPa |
| Hastelloy C276 | ¼, ⅜ and ½ in | 33 100 – 35 170 kPa |
| Titanium Gr 2 | ¼ × 0.035 · ⅜ × 0.049 · ½ × 0.065 | 31 000 · 28 960 · 28 960 kPa |
Adapted from a Prochem installation-training learners' guide (Nov 2024), referencing a project general instrumentation specification and operations tubing & fitting management strategy. For information only — always work from the current controlled revision.
Select a part of the fitting to learn what it does.
The front ferrule is driven into the body's tapered bore. It seals against the body and on the tube OD.
Field check: Both ferrules fitted, the right way round, from the same manufacturer as the body.
Two-ferrule fittings from different manufacturers work on the same principle, but each has its own geometry, gauges and instructions. The fitting used as the worked example in the Prochem installation training is the HOKE GYROLOK®: a body, front ferrule, rear ferrule and nut, supplied assembled and ready to use. Keep them boxed and clean until needed.
15° angles between the nut, rear ferrule and front ferrule close up during make-up and lock the small rear ferrule at 1¼ turns. It grips hard enough to hold to burst pressure, but won't over-cut the tube OD or squeeze down the ID if over-tightened.
Stops the body flaring and the nut jamming when over-tightened. On fittings without this feature, an over-tightened rear ferrule can wedge the front ferrule outward and flare the body until it can't be reused.
A square-cut, deburred tube end seals against the bottom of the body — a secondary seal that removes dead space for cleaner sampling and faster vacuum pump-down. Don't rely on it to excuse scratched tube.
A taper at the bottom of the tube socket. The tube stops on the taper, then is driven forward as the nut is tightened — reducing galling and "tube sticking" when the fitting is later taken apart.
The ferrules only touch the tube. Nothing is set yet.
The rear ferrule pushes the front ferrule into the body taper, making the seals to the tube and to the body. The front ferrule grabs the tube and drives it to the base of the sizing angle.
With the tube bottomed, the rear ferrule (the hardest part of the system) sets and grips the tube to resist pull-out and vibration.
| Part number | Means |
|---|---|
4CM4-316 | ¼ in (4/16) tube × connector male × ¼ in NPT thread, 316 stainless |
8LM4-316 [EC] | ½ in tube × elbow male × ¼ in thread; modifier changes thread to BSPT |
6RU3-BR [ME] | Reducing union, brass — metric tube × fractional tube; the [ME] modifier marks the metric end |
Fractional sizes are in sixteenths of an inch. Tees are coded run (ports 1 and 2) then branch (port 3): a TTM has tube at 1 and 2 with a male pipe thread on the branch; a TFT has tube at 1 and 3 with a female thread at 2. Confirm codes in the current catalogue.
Most tube runs end at a threaded port — on a valve, manifold or instrument. A tapered pipe thread is a common leak and blow-out point, so know how it seals, how much engagement to expect, which sealant is approved for the service, and how to design threads out altogether.
National Pipe Taper (NPT) threads are made to ASME B1.20.1. The thread form has a 60° flank angle, flat (truncated) crests and roots — sharper-looking than the rounded Whitworth/BSP form — and a number of threads per inch that depends on the nominal pipe size. Male and female threads both taper at 1 in 16 on diameter (1° 47′).
The joint seals as the two tapers wedge together. Pressure-tight joints are made up wrench-tight with a sealant; on stainless steel the sealant also lubricates the threads to prevent galling.
Site example: operations tubing & fitting management strategy. Your site's approved-sealant list takes precedence.
| 1 in NPT, hand-tight (ASME B1.20.1) | Engagement |
|---|---|
| Minimum (male and female at L1 − 1 pitch) | 2.6 threads · 5.74 mm |
| Nominal (both at L1) | 4.6 threads · 10.16 mm |
| Maximum (both at L1 + 1 pitch) | 6.6 threads · 14.57 mm |
Because the standard allows ±1 pitch, a fully assembled ASME fitting may have only 2–3 threads engaged, leaving 4–5 visible. Tighter-tolerance fittings (the HOKE thread specification is 62.5% tighter) typically engage 5–6 threads, leaving 1–2 visible — a stronger joint that better resists vibration and corrosion.
The site-example specification tightens the ASME L1 gauging tolerance to L1 + ¼ to L1 + 1 turn:
Use an approved sealant on every new pressure-tight threaded joint. Thread tape is preferred for new installations. Sealing paste may be used where it already exists within a package, where it is common industry practice (rotating equipment, hydraulic systems), or where the service temperature exceeds the tape's limit. If operations can't allow at least a 3-hour cure before pressurising, use only thread tape or Grafoil GTS paste — depending on the service temperature.
Instrument tappings have traditionally used a piping-class double block and bleed (DBB) assembly with extra small-bore instrument valves screwed on. A typical conventional 1 in, 1500# multi-valve DBB tapping:
It also needs a support bracket and on-site assembly, is prone to vibration fatigue, and puts a bending moment on the branch weld.
Use a rotary wheel tube cutter with a sharp wheel, cutting square to the tube centreline. The end must be truly round and free of defects. Many site specifications do not permit saws or power tools for instrument tube.
Remove burrs from the inside and outside without chamfering the OD. Blow the tube through with clean, dry air to remove swarf. Burrs cause poor ferrule set; contamination blocks impulse lines and damages analysers.
No scratches, dents or ovality where the ferrules will sit. Keep enough straight length between a bend and the fitting.
Use the manufacturer's marking tool (for example the GYROLOK® GMT) to mark insertion depth with a low-chloride marker. Slide the nut back to check both ferrules face the right way, then push the tube until it bottoms firmly and tighten the nut finger-tight. The mark must not be visible — if it is, the tube isn't seated or a ferrule is missing.
Mark the nut at the 6 o'clock position, and the body alongside it, so you can count turns accurately.
Hold the body steady with a backup wrench and turn the nut the number of turns the manufacturer specifies.
Try the manufacturer's inspection gauge in the nut-to-body gap — if it enters, the fitting is not tight enough. With a marking tool, the insertion mark should now be visible just behind the nut.
Typical two-ferrule values shown: 1¼ turns for ¼–1 in (6–25 mm), ¾ turn for small-bore sizes. Always use the fitting manufacturer's instructions for the exact product.
Insert the tube with its set ferrules until it bottoms, and tighten the nut hand-tight. Then tighten it back to its earlier position — you will feel a sharp rise in torque — and snug it slightly. For GYROLOK® this is a ¼ turn past hand-tight. Never swap used ferrules between fittings, and replace any part that is damaged.
Large or hard tube needs more force than a hand wrench can apply consistently. A pre-setting tool (PST) — a hardened fitting-end held in a vice — lets you set the ferrules on the bench and then install them in place. A hydraulic pre-setting tool (HPST) sets ferrules on ½–2 in (12–38 mm) tube with interchangeable dies, and cuts final manual make-up torque by about 30%.
Based on the GYROLOK® "when to use what procedure" chart and the site rule (OT&FMS 9.1): an HPST shall be used, unless there isn't enough clearance, for non-316 tube of ½ in OD and above, and 316 tube above ½ in OD.
| Operation | Wrench turns | Check |
|---|---|---|
| First make-up (manual, in the body or a PST) | 1¼ | Mark nut and body first; GMT line not visible at hand-tight, visible after |
| Remake a previously made-up fitting | ¼ | Ferrules already set; hand-tight, then ¼ turn |
| Install an HPST pre-set, tube up to 1 in (25 mm) | ½ | After the indicator arm has released |
| Install an HPST pre-set, tube above 1 in (25 mm) | ¾ | After the indicator arm has released |
| Integral (male-nut) connection in a valve or manifold body | 1¼ new · ¼ remake | Support the valve body, not the tube |
| Plug into a fitting body | ¼ | Hand-tight first |
| Cap onto a tube end | 1¼ | Tube fully bottomed in the cap |
| Port connector (machined-ferrule end) | ¼ | Then make up the tube-stub end as a new fitting |
Turn counts differ between manufacturers, sizes and wall thicknesses. Always use the instructions for the exact fitting in your hand.
A good bend cuts down on fittings (and potential leak points), keeps the bore round and puts no load on the connection. Use a bender sized for the tube OD. Never kink, flatten or wrinkle the tube.
The tube must run straight far enough into the fitting to bottom fully, give correct ferrule action, leave room for the nut to travel and allow easy disassembly. A bend that starts too close to the fitting stops the tube seating and loads the ferrules. Never bend tube after it has been inserted into a fitting.
| Tube OD (T) | Min. bend radius (R) | Min. straight length (L) | Recommended distance before first mark |
|---|---|---|---|
| ¼ in | 9/16 in (14 mm) | 25 mm | 39 mm |
| ⅜ in | 15/16 in (24 mm) | 25 mm | 43.6 mm |
| ½ in | 1½ in (38 mm) | 40 mm | 64 mm |
| ¾ in | 1¾ in (44 mm) | 50 mm | 71.5 mm |
| 1 in | 3 in (76 mm) | 50 mm | 111.1 mm |
GYROLOK® planning values. Check your bender and fitting manufacturer's data for other brands and wall thicknesses.
Take the tapping from the top or side of the pipe and slope the line continuously up to the transmitter so any condensed liquid drains back into the process.
Risk if wrong: liquid collects in low points and adds a false hydrostatic head.
| Tube OD | Typical industry span | Site example |
|---|---|---|
| ¼ in (6 mm) | about 0.9 m | 0.5 m |
| ⅜ in – ½ in (10–12 mm) | 0.9 – 1.2 m | 1.0 m |
| ¾ in (20 mm) | about 1.2 m | 1.5 m |
| 1 in (25 mm) | about 1.5 m | 2.0 m |
In the offshore site example, tube runs longer than 1000 mm are also supported at least every 1000 mm, and within 250 mm of any bend. Support a fitting close by on both sides where there is vibration or heavy components. Project specifications take precedence.
Test medium, pressure, hold time and acceptance criteria come from the approved procedure (see the site example below). Never exceed the lowest-rated component in the system.
Isolate instruments that could be overpressured. Set up barriers and exclusion zones, and use a regulated source with relief protection.
Raise pressure in steps, stopping to check for movement and leaks.
Apply a leak-detection fluid to every connection. For pressure-decay tests, record the start and end pressure and the temperature.
Never tighten a fitting under pressure. Vent safely, fix the fault, then retest.
Never exceed the rating of the lowest-rated component, and follow the approved pressure-test plan. Pneumatic testing stores far more energy than hydrostatic testing — exclusion zones matter.
Six scenarios to check your understanding. For the full scored assessment and records, open the workbook.
Identification drills, a make-up sequencing exercise, bend calculations, fitting and leak-test records, and a scored final assessment. Your answers save automatically and print as a clean record.
Training boundary: This course provides general awareness of instrument tubing practice. Turn counts, pressure ratings, sealant selections, support spacing and slopes are typical or site examples only (site examples are drawn from a Prochem installation-training guide). Always follow the fitting manufacturer's instructions, project specifications, approved procedures, permits and pressure-test plans, and work only within your authorised competency.